...
Home    >    News    >    Industry Updates    >    How to Wire 1NO/1NC and 2NO2NC Contacts (Step-by-Step With Diagrams)

How to Wire 1NO/1NC and 2NO2NC Contacts (Step-by-Step With Diagrams)

2025-09-08

Step-by-step 1NO 1NC wiring guide with diagrams for safe, accurate push button and contactor connections in control panels and machines.

Wiring 1NO 1NC and 2NO2NC contacts requires you to identify the correct terminals and connect each wire with care. You should always use a step-by-step wiring guide to ensure safety and accuracy. In real-world projects, a reliable push button switch from CODE helps you achieve dependable results. With the right approach, you can master 1NO 1NC wiring for control panels and machines.

Key Takeaways

  • Understand the difference between Normally Open (NO) and Normally Closed (NC) contacts. NO contacts allow current to flow only when activated, while NC contacts stop current when activated. This knowledge is crucial for safe and effective wiring.

  • Always prioritize safety by following a lockout/tagout procedure before starting any wiring. This prevents accidental energization and protects both you and your equipment during the wiring process.

  • Use the correct terminal numbers when wiring push button switches. Familiarize yourself with the IEC standard terminal numbers to avoid mistakes and ensure proper connections.

  • Gather all necessary tools and components before starting your wiring project. Having the right tools on hand, like screwdrivers and multimeters, helps you work efficiently and safely.

  • Test your wiring with a multimeter before applying power. This step helps you confirm that all connections are correct and functioning as intended, reducing the risk of errors.

Introduction: What 1NO/1NC and 2NO2NC Mean

When you work with push button switches, you often see terms like 1NO/1NC or 2NO2NC. These labels describe the number and type of contacts inside the switch. Understanding these terms helps you wire your control circuits correctly and safely.

NO vs NC Defined by De-energized State

You need to know how contacts behave when no power is applied. Normally Open (NO) and Normally Closed (NC) contacts act differently in their default, or de-energized, state.

Contact Type

Default State (De-energized)

State When Energized

Normally Open (NO)

Circuit is broken (off)

Circuit completes (on)

Normally Closed (NC)

Circuit is complete (on)

Circuit breaks (off)

  • Normally Open (NO) Contacts: In the default state, the circuit stays open. No current flows. When you press the button or energize the coil, the contact closes and current flows.

  • Normally Closed (NC) Contacts: In the default state, the circuit stays closed. Current flows. When you press the button or energize the coil, the contact opens and current stops.

You use NO contacts to start a process or send a signal only when you press the button. You use NC contacts for safety or to stop a process when the button is released.

IEC Terminal Numbering Cheat Sheet

You will see numbers on the side of most industrial push button switches. These numbers follow the IEC standard and help you connect wires to the right terminals.

13-14 NO, 21-22 NC, A1/A2 Coil

Here is a quick reference for common terminal numbers:

Terminal Number

Description

1

Common for the N.C. contact

2

The N.C. contact

3

Common for the N.O. contact

4

The N.O. contact

For example, terminals 13 and 14 usually mark a NO contact, while 21 and 22 mark a NC contact. A1 and A2 are for the coil in relays or contactors.

Contact Symbols (IEC vs NEMA)

You may notice different symbols on diagrams. IEC uses simple lines and numbers, while NEMA uses letters and shapes. Always check the legend on your wiring diagram. This helps you match the right contact type and terminal number, no matter which standard you use.

Tip: Always double-check the terminal numbers before wiring. This prevents mistakes and keeps your circuit safe.

Safety First

Before you start making any connections, you must always put safety first. Working with electrical circuits can be dangerous if you skip important steps. You protect yourself and your equipment by following strict safety procedures.

Lockout/Tagout and Voltage Verification

You should always follow a lockout/tagout process before wiring push button contacts. Here is a step-by-step guide:

  1. Isolate equipment by disconnecting it from all energy sources.

  2. Apply lockout/tagout devices. Use locks and tags on power sources to prevent accidental start-up.

  3. Check that all energy is drained from the equipment.

  4. Verify isolation. Confirm that the equipment is truly disconnected.

  5. Turn off all controls. Set switches to the ‘off’ or neutral position.

  6. Return to service only after removing all tools and making sure everything is safe.

After lockout/tagout, you need to verify that no voltage remains. Start with a non-contact voltage tester for a quick check. Always follow up with a contact voltage tester to confirm the area is safe. Test both phase-to-phase and phase-to-ground. This double-check ensures your connections will not put you at risk.

Ratings, IP and Wire Size Checks

You must select the right wire size and protection level for your connections. For power circuits, use at least 14 AWG wire. For lighting and control circuits, 16 AWG is the minimum. If your control circuits stay inside an enclosure, you can use 18 AWG. For electronic I/O, you may use 24 AWG or smaller, depending on the setup.

You also need to check the IP rating of your equipment. Use at least IP4X on horizontal surfaces and IP2X on vertical surfaces. This protects your connections from dust and accidental contact.

When E-Stops and Safety Functions Apply

Emergency stop (E-Stop) buttons and safety functions play a key role in many control panels. You should use E-Stops in any system where a quick shutdown could prevent injury or damage. Always wire E-Stops using NC contacts for reliable safety connections.

Mechanical Interlock and Mirror Contacts (Overview)

Mechanical interlocks prevent two circuits from closing at the same time. This feature keeps your connections safe in systems with opposed motions. Mirror contacts provide feedback to your control system. They help you monitor the real status of your connections and improve safety.

Tools and Parts You’ll Need

Before you start wiring 1NO/1NC or 2NO2NC contacts, you should gather all the right tools and components. Having everything ready helps you work safely and efficiently.

Tools Checklist

You need a few basic tools to wire push button stations. These tools help you strip wires, tighten screws, and check your work.

  • Screwdrivers: Use both flathead and Phillips types for terminal screws.

  • Wire Strippers: Remove insulation from wires without damaging them.

  • Needle-Nose Pliers: Bend and hold wires in tight spaces.

  • Multimeter: Test for voltage and check continuity.

  • Crimping Tool: Attach ferrules or terminals to wire ends.

  • Label Maker or Markers: Mark wires for easy identification.

  • Insulation Tape or Heat Shrink: Cover exposed connections for safety.

Tip: Always use insulated tools when working with electrical circuits. This keeps you safe from accidental shocks.

Typical Components

You need several key parts to build a reliable push button station. Each part plays a specific role in the system.

1NO/1NC and 2NO2NC Blocks

You use contact blocks to create the switching action. A 1NO/1NC block gives you one normally open and one normally closed contact. A 2NO2NC block provides two of each. These blocks snap onto the back of the push button switch. You can choose the right block based on your control needs.

You also need:

  • Enclosure: Shields the internal parts from dust and moisture.

  • Push Buttons & Switches: Let you control the circuit with a simple press.

  • Wiring Harness: Connects all the devices and delivers power or signals.

  • Terminal Blocks: Keep your wiring neat and organized.

  • Legend Plates: Label each button so operators know what each one does.

Contactor, Overload, Pilot Lamp

For more advanced control, you may add:

  • Contactor: Acts as a heavy-duty relay to switch larger loads.

  • Overload Relay: Protects motors and circuits from drawing too much current.

  • Pilot Lamp: Shows the status of the circuit with a clear light signal.

To wire an indicator lamp, you connect one pin to either the common or the NO/NC terminal. Choose the connection based on when you want the lamp to light up—when the button is pressed or released.

Note: Using high-quality push button switches from CODE ensures your control panel works reliably in any environment.

Wiring Fundamentals

COM–NO–NC Terminals on Push Buttons

When you wire a push button switch, you need to understand the role of each terminal. Most push buttons use three main terminals: Common (COM), Normally Open (NO), and Normally Closed (NC). Each terminal serves a specific function in your circuit.

You can find different terminal arrangements depending on the type of push button. The table below shows common setups:

Terminal Type

Connection Description

2-Pin (NO Only)

COM to feed, NO to load

4-Pin (NO + LED)

COM to feed, NO to load, LED+ to +24 V supply, LED− to common return

5-Pin (NO + NC + LED)

COM to feed, NO to load, NC to safety circuit, LED+ to + supply, LED− to ground

You connect the power source to the COM terminal. For a basic start function, you run a wire from the NO terminal to your load or control input. If your switch includes an NC terminal, you can use it for safety circuits or to break a circuit when the button is pressed. LED terminals allow you to add visual feedback.

Tip: Always check the wiring diagram on your push button or in the product manual before making connections.

Using a Multimeter to Test Contacts

Testing your push button contacts before installation helps you avoid wiring mistakes. You can use a multimeter to check if the NO and NC contacts work as expected.

Continuity Tests (NO/NC Before and After Actuation)

Follow these steps to test your contacts:

  1. Ensure safety. Turn off power at the breaker and verify with a voltage tester.

  2. Select continuity test mode on your multimeter.

  3. Check your multimeter by touching the probes together. You should hear a beep.

  4. Disconnect the switch from the circuit.

  5. Attach one probe to each terminal you want to test.

When you press the button, the NO contact should close (beep), and the NC contact should open (no beep). Release the button to see the opposite result.

Labeling, Ferrules, and Cable Management

Good labeling and cable management make your wiring safe and easy to maintain. Use a label maker or write clearly on each wire. Crimp ferrules onto wire ends for secure connections. Bundle wires neatly with cable ties or wire ducts. This keeps your control panel organized and reduces troubleshooting time.

Proper labeling and cable management help you and others quickly identify circuits and prevent wiring errors.

Scenario A — Wiring a 1NO/1NC Push Button (Standalone)

Option 1 — Use NO for a Control Input

When you want to use a push button to start a process or send a signal, you usually use the Normally Open (NO) contact. This setup means the circuit stays off until you press the button.

Step 1: Power → COM → NO → Input

You need to connect the wires to the correct terminals. The table below shows a typical wiring scheme for a 1NO/1NC push button:

Wire Color

Connection Description

Green

Connect to power source’s positive pole (C public wire)

Blue

Connect to NO line

Red

Join with positive pole of controlled appliance (LED)

Black

Connect to negative pole of controlled appliance (LED)

Yellow

Connect to NC wire

Start by connecting the green wire to the power source. Attach the blue wire to the NO terminal. The red and black wires go to the LED indicator if you want a visual signal. The yellow wire connects to the NC terminal, but you do not use it in this basic NO setup.

Step 2: Return Path and Indicator Lamp

You can add an indicator lamp to show when the circuit is active. Connect one side of the lamp to the output from the NO terminal. Connect the other side to the return or ground. When you press the button, the lamp lights up, showing the circuit is complete.

Tip: Always double-check your connections before applying power. This step helps prevent wiring errors and keeps your equipment safe.

Option 2 — Use NC for Fail-Safe Monitoring

You may need to use the Normally Closed (NC) contact for safety. This setup keeps the circuit on until you press the button, which then breaks the circuit.

Step 1: Power → COM → NC → Input

Connect the power source to the common terminal. Run a wire from the NC terminal to your control input. This arrangement ensures the circuit stays complete until you press the button.

Step 2: Test for Open on Fault/Disconnection

Using NC contacts gives you several important advantages:

  • NC contacts provide safety. Pressing the button opens the circuit and stops machinery right away.

  • This setup creates a fail-safe design. If a wire breaks, the circuit opens and keeps equipment safe.

  • NC contacts follow industry standards. Operators can easily understand their function.

  • The operation is logical and reduces human error during emergencies.

  • If the NC contact gets stuck open, the machine will not start. This alerts maintenance staff to check for problems.

  • In case of disconnection or damage, the control system detects the loss of signal and stops the machine safely.

Note: Using NC contacts for safety circuits helps you meet industry requirements and keeps your workplace secure.

Scenario B — Start/Stop Station With a Contactor (Seal-In)

Three-Wire Control Logic Explained

You often see three-wire control logic in industrial start/stop stations. This method uses a STOP button (normally closed), a START button (normally open), and a contactor coil. You gain several advantages when you use this setup:

  • The separation of start and stop commands minimizes accidental operations, enhancing safety.

  • You can troubleshoot and maintain each function independently, which improves reliability.

  • The system provides consistent motor performance and reduces mechanical stress.

Three-wire control logic helps you create a safe and dependable control circuit. You can stop the motor instantly or start it only when you press the correct button.

Step-by-Step Wiring

You can wire a start/stop station with a contactor and seal-in circuit by following these steps:

Step 1: Power → STOP (NC) → START (NO) → A1; A2 Return

  1. Wire the incoming power to the contactor by connecting three-phase power to terminals 1/L1, 3/L2, and 5/L3.

  2. Connect the STOP button (NC) in series with the START button (NO). Run this circuit to the A1 terminal of the contactor coil.

  3. Connect the A2 terminal of the coil to the neutral or negative side of your power supply.

Step 2: Add Auxiliary NO (13-14) in Parallel With START (Seal-In)

  1. Wire the NO auxiliary contact (13-14) in parallel with the START button. This creates a seal-in circuit, keeping the contactor energized after you release the START button.

Step 3: Insert Overload NC in Series With Coil

  1. Place the overload relay’s NC contact in series with the coil circuit. This protects the motor by breaking the circuit if an overload occurs.

Step 4: Add Pilot Lamp Indication (Parallel to Coil or Via Aux)

  1. Connect a pilot lamp in parallel with the coil or through the auxiliary contact. The lamp lights up when the motor runs, giving you a clear status indication.

Step 5: Commissioning Checks and Functional Test

  1. Double-check all connections. Test the STOP and START buttons to confirm proper operation. Verify that the seal-in circuit holds the contactor and that the overload relay interrupts the circuit during a fault.

Tip: Always use high-quality push button switches from CODE for reliable performance in your control panels.

Scenario C — Wiring 2NO2NC Contacts

When you work with 2NO2NC contacts, you gain flexibility for complex control panels. You have two normally open and two normally closed contacts, which lets you manage multiple signals and safety functions at once.

Use Case 1 — Extra Signals to PLC/Indicators

You often need to send extra signals to a PLC or indicator lights. With 2NO2NC contacts, you can use one set of normally open contacts for seal-in circuits and another for PLC inputs. The normally closed contacts help you create interlocks or trigger alarms.

One NO for Seal-In, One NO for PLC Input

You connect one set of wires from a normally open contact to maintain the seal-in function. The second set of wires from the other normally open contact goes to the PLC input. This setup allows you to control both the main circuit and send a status signal to your automation system.

Connection Type

Description

NC Signal

The PLC input connects to the normally closed output wires, activating only during an alarm.

Power Polarity

Reversing the power polarity on the blue and brown wires changes the output state for alarms.

Indicator Lights

The sensor works normally, but the PLC input stays unchanged until an alarm triggers.

NC Contacts for Interlocks or Alarms

You use the normally closed contacts to create interlocks between machines or trigger alarms. When a fault occurs, the wires from the normally closed contacts break the circuit, stopping equipment or alerting operators. This design improves safety and helps you meet industrial standards.

Tip: Always label your wires clearly when wiring both normally open and normally closed contacts. This makes troubleshooting easier.

Use Case 2 — Multi-Station Start/Stop With Master Stop

You can wire several start/stop stations using 2NO2NC contacts. This setup lets you control machines from different locations and add a master stop for safety.

Parallel STARTs, Series STOPs Topology

You connect all start buttons in parallel using wires from the normally open contacts. This means pressing any start button energizes the circuit. You wire all stop buttons in series using the normally closed contacts. If any stop button is pressed, the circuit opens and the machine stops.

  • You use a latching mechanism with auxiliary normally open contacts to keep the motor running after you release the start button.

  • The master stop button uses wires from the normally closed contacts to interrupt power to all motor contactors.

  • Time-delay relays can be added to the normally open circuit to prevent premature startup or direction reversal.

Adding Mechanical Interlock for Opposed Motions

You can add mechanical interlocks using the normally closed contacts. This prevents two motors from running in opposite directions at the same time. The wires from the normally closed contacts break the circuit if both directions are selected, keeping your system safe.

Note: Using both normally open and normally closed contacts with separate wires gives you more control and safety in your panel design.

Testing and Commissioning

Testing and commissioning your push button circuits ensures everything works as designed. You should always follow a step-by-step process before putting your system into service.

Cold Tests (No Power) and Live Tests (Low Voltage First)

Start with cold tests. These tests check your wiring for safety before you apply power. Use a multimeter to check for continuity and insulation resistance. This step helps you find wiring errors or shorts.

Test Type

Purpose

Cold Test

Checks insulation resistance and continuity of circuits before energizing.

Live Test

Conducted with special equipment to check the integrity of electrical installation and effective operation as per designed parameters.

After cold tests, move to live tests. Always use low voltage first. This approach keeps you safe and protects your equipment. Follow this sequence:

  1. Test a known live source to confirm your tester works.

  2. Verify the target circuit is de-energized.

  3. Test a known live source again to ensure your tester remains reliable.

Tip: Always compare your results with the wiring diagram. This step helps you spot mistakes before they cause problems.

Verification Checklist

A good verification checklist helps you confirm that your NO/NC contacts work as intended. You should check each function against your wiring diagram and system requirements.

Directional Logic, Seal-In Behavior, Drop-out on Power Loss

Check that each contact behaves as expected. For example, a DRY NC contact should stay closed in normal conditions and open during a trip. A DRY NO contact should stay open and only close when an alarm or command occurs. Use this table to guide your checks:

Use case

Recommended contact

Normal state

Action state

Rationale

High-temperature / high-pressure trip

DRY NC

Closed

Opens on trip

If the loop breaks or card loses power, it opens → trip stays safe

Low-level alarm

DRY NO

Open

Closes on alarm

If the loop breaks, it remains open → avoids spurious alarm

Remote start command

DRY NO

Open

Closes to start

Prevents unintended starts on wire short or idle noise

Emergency stop (ESD)

DRY NC

Closed

Opens to stop

Break = stop; the safest behavior

Test seal-in circuits by pressing the start button and checking if the contactor holds. Simulate a power loss to see if the circuit drops out as it should.

Torque, Marking, IP and Strain Relief

Check that all terminal screws are tight. Loose connections can cause failures. Make sure each wire is marked clearly. Confirm that your enclosure meets the correct IP rating. Use strain reliefs to protect wires from pulling or bending.

Note: Always use your wiring diagram during commissioning. This habit ensures every connection matches your design.

Troubleshooting and Common Mistakes

When you wire push button circuits, you may run into a few common problems. Knowing how to spot and fix these issues helps you keep your control panels safe and reliable.

Seal-In Not Holding

A seal-in circuit keeps the contactor energized after you press the START button. If your circuit does not hold, you need to check a few things.

Missing Auxiliary Parallel or Wrong Terminal Numbers

  • You may forget to wire the auxiliary NO contact (13-14) in parallel with the START button. Without this connection, the circuit drops out as soon as you release the button.

  • Double-check the terminal numbers. If you connect wires to the wrong terminals, the seal-in will not work.

  • Always use the wiring diagram for your specific push button switch. This step helps you avoid mistakes with terminal assignments.

Tip: Mark each wire with its function and terminal number. This habit makes troubleshooting much easier.

Indicator Works Backwards

Sometimes, the indicator lamp lights up when it should be off, or stays off when it should be on. This problem often comes from wiring or polarity errors.

NO/NC Miswired or Wrong Supply

  • LEDs need correct polarity. If you reverse the connections, the LED may only light in one direction or not at all.

  • If you connect the indicator to the wrong side of the switch, it may show the opposite status.

  • Try replacing the LED with a standard bulb to see if the problem is with polarity.

  • Make sure the indicator connects to the correct terminals for the intended function.

Note: Always check the wiring diagram and the LED’s polarity markings before installation.

Coil Not Energizing

If the contactor coil does not pull in, your machine will not start. Several issues can cause this.

Incorrect Coil Voltage, Overload NC Open, STOP Loop Open

  • Check that the coil voltage matches the supply voltage. A mismatch prevents the coil from energizing.

  • If the overload relay trips or the NC overload contact opens, the coil circuit breaks.

  • Inspect the STOP button. If it is open or dirty, power cannot reach the coil.

  • Trace the control circuit. Look for loose wires, open switches, or faulty connections.

  • Manually press the contactor to see if it engages. If it does, the problem is in the start circuit wiring.

Always verify each part of the control circuit step by step. Careful checks help you find and fix the issue quickly.

Pro Tips and Compliance Notes

Choose Pilot-Duty Ratings for Control Circuits

When you select components for control circuits, always check the pilot-duty rating. This rating tells you if a device can handle the electrical load in control applications. You want to avoid early failures and ensure safe operation.

  • Many control circuits use relays or contactors to switch loads like solenoids or small motors.

  • For example, a relay controlling a solenoid at 48 VDC with an R300 pilot duty rating can safely switch up to 0.6 amps. This matches the requirements set by NEMA standards.

  • NEMA standards also state that most DC inductive loads in control circuits are relays, contactors, or solenoids rated at 50 watts or less.

Tip: Always match your push button switch and relay ratings to the load. This step prevents overheating and extends the life of your control panel.

NO/NC Selection for Diagnostics and Reliability

Choosing between Normally Open (NO) and Normally Closed (NC) contacts affects how your system works and how easy it is to diagnose problems.

  • NO contacts activate only when a condition is met. You use them for general control tasks.

  • NC contacts stay closed by default. They open only when needed, which is important for safety-critical circuits.

  • NC contacts help you maintain circuit closure under normal conditions. This design ensures the system works unless a fault or emergency occurs.

Note: In safety systems, NC contacts provide a reliable way to interrupt power during emergencies.

Using Mirror Contacts for Feedback

Mirror contacts give you feedback about the real status of your circuit. You can connect these contacts to a PLC or indicator light. This setup helps you monitor if a relay or contactor has truly changed state.

  • Mirror contacts improve diagnostics. You can quickly spot if a device fails to operate as expected.

  • They add an extra layer of safety by confirming the actual position of contacts.

When to Upgrade to Safety-Rated Devices

You should consider safety-rated devices when your application involves people or critical equipment. Safety-rated push button switches and contact blocks meet strict standards for reliability.

  • Upgrade to safety-rated devices for emergency stops, machine guarding, or hazardous locations.

  • These devices often include features like mechanical interlocks or mirror contacts for extra assurance.

Using CODE’s high-quality push button switches helps you meet compliance and safety goals in demanding environments.

Diagrams Included

1NO/1NC Terminal Map and Symbols

You often see terminal maps and symbols on push button switches. These diagrams help you connect wires to the correct terminals. A typical 1NO/1NC push button has three main terminals: Common (COM), Normally Open (NO), and Normally Closed (NC). You can use the following table to understand the basic layout:

Terminal Number

Symbol

Description

13-14

NO

Normally Open Contact

21-22

NC

Normally Closed Contact

A1/A2

Coil

Coil Terminals (if present)

You will also see symbols on wiring diagrams. The NO contact symbol looks like two lines that do not touch. The NC contact symbol shows two lines that touch. Always match the terminal numbers and symbols before you start wiring.

Start/Stop With Seal-In and Overload

A start/stop station with seal-in and overload protection uses a 3-wire control circuit. This setup gives you safe and reliable motor control. You use both normally open and normally closed contacts. The seal-in contact keeps the motor running after you release the start button. The stop button or an overload condition will break the circuit and stop the motor.

Here is a table that shows each component and its function:

Component

Function

Start Pushbutton

Starts the motor when pressed.

Seal-in Contact

Keeps the motor running after you release the start button.

Overload Contacts

Stops the motor if an overload happens.

Stop Pushbutton

Stops the motor when pressed.

Jog Position Switch

Lets you run the motor for a short time by holding the switch.

  • You use a 3-wire control circuit for most start/stop stations.

  • The seal-in contact allows the motor to keep running after you let go of the start button.

  • The stop button or overload contact will always stop the motor.

Tip: Always check your wiring diagram before you connect any wires.

2NO2NC Multi-Signal and Master Stop Schematics

A 2NO2NC push button gives you more options for control and safety. You can send multiple signals or add extra safety features. For example, you can use one NO contact for a seal-in circuit and another for a PLC input. The NC contacts can provide interlocks or alarms.

You can wire several start buttons in parallel using the NO contacts. This lets you start a machine from different locations. You can wire stop buttons in series using the NC contacts. Pressing any stop button will stop the machine. You can also add a master stop for extra safety.

Note: Using clear diagrams and labels helps you avoid mistakes and makes troubleshooting easier. Always follow the recommended wiring practices for your application.

FAQs

What Do 13-14 and 21-22 Mean?

You often see numbers like 13-14 and 21-22 on push button switches. These numbers help you find the right terminals for wiring.

  • 13-14: This pair marks a Normally Open (NO) contact. When you press the button, the circuit closes and current flows.

  • 21-22: This pair marks a Normally Closed (NC) contact. When you press the button, the circuit opens and current stops.

Tip: Always check the terminal numbers before you connect wires. This step helps you avoid wiring mistakes.

Can I Parallel the START Button With an Auxiliary NO?

Yes, you can. You often use this method in a seal-in circuit.

  • Connect the auxiliary NO contact (like 13-14) in parallel with the START button.

  • When you press START, the circuit energizes the contactor coil.

  • The auxiliary NO contact then closes and keeps the circuit on, even after you release the START button.

This setup lets your machine keep running until you press the STOP button.

When Should I Use 2NO2NC Instead of 1NO1NC?

You should use 2NO2NC contacts when you need more control options.

  • Use 2NO2NC if you want to send extra signals to a PLC or indicator lights.

  • Choose 2NO2NC for multi-station control or when you need more safety interlocks.

  • 1NO1NC works well for simple start/stop tasks. 2NO2NC gives you more flexibility for complex panels.

Contact Block

Best Use Case

1NO1NC

Basic control, single signal

2NO2NC

Advanced, multi-signal tasks

How Do I Test NO/NC With a Multimeter?

You can test NO and NC contacts with a multimeter set to continuity mode.

  1. Turn off power to the circuit.

  2. Place one probe on the COM terminal and the other on the NO or NC terminal.

  3. For NO: The meter should not beep. Press the button—now it should beep.

  4. For NC: The meter should beep. Press the button—it should stop beeping.

Note: Always test with the power off to stay safe.

Conclusion and Next Steps

You now have the knowledge to wire 1NO/1NC and 2NO2NC contacts with confidence. You understand the importance of safety, correct terminal identification, and step-by-step wiring. You can apply these skills to real-world control panels and machines. Using high-quality push button switches from CODE ensures your circuits remain reliable and safe in any environment.

Downloadable Checklist and Printable Diagrams

To help you succeed, you can use a handy checklist and clear diagrams. These resources guide you through each step and help you avoid common mistakes.

Wiring Checklist:

  • Verify power is off and locked out

  • Identify all NO and NC terminals

  • Use correct wire size and type

  • Label every wire clearly

  • Double-check connections with a multimeter

  • Test all functions before powering up

Tip: Download the full checklist and printable wiring diagrams from CODE’s official website. These tools make your projects easier and safer.

You can print these diagrams and keep them in your workshop. They serve as quick references during installation and troubleshooting.

Related Guides: Emergency Stops, Indicator Lights, and Contactor Basics

You can expand your skills by exploring more guides. Each topic builds on what you learned in this blog.

  • Emergency Stops: Learn how to wire E-Stop buttons for maximum safety.

  • Indicator Lights: Discover how to add visual signals to your control panels.

  • Contactor Basics: Understand how contactors work and how to wire them for different applications.

For more detailed instructions and product solutions, visit CODE’s resource center. You can find expert advice and high-quality components for every project.

With these resources, you can create safer, smarter, and more efficient control systems. Start your next project with confidence and let CODE help you create a better future together.

You now understand the essential steps for 1no 1nc wiring and how to apply these skills to 2NO2NC contacts. Always start with a clear diagram before any 1no 1nc wiring. Use the correct circuit connection for each application. Choose CODE’s push button switches for reliable 1no 1nc wiring every time. Follow safety rules and double-check your 1no 1nc wiring. Visit CODE’s website to explore more solutions for your next 1no 1nc wiring project.

FAQ

What do 1NO and 1NC mean on a push button switch?

You see 1NO for “one normally open” contact and 1NC for “one normally closed” contact. 1NO closes the circuit when pressed. 1NC opens the circuit when pressed. These contacts help you control different functions in your panel.

How do you identify the correct terminals on a CODE push button?

You find terminal numbers printed on the switch body. For example, 13-14 marks NO, and 21-22 marks NC. Always check the product manual or diagram. This step helps you avoid wiring mistakes.

Can you use both NO and NC contacts at the same time?

Yes, you can. You connect each contact to a different part of your circuit. For example, use NO to start a device and NC to stop or signal a fault. This setup gives you more control options.

Why should you test contacts with a multimeter before wiring?

Testing with a multimeter ensures each contact works as expected. You avoid wiring errors and prevent equipment damage. Always test for continuity before installation. This habit keeps your projects safe and reliable.

Share:

YOU MIGHT BE INTERESTED IN THIS

We keep you up to date.

For inquiries about our products or pricelist, please leave your email to us and we will be in touch within 24 hours.

Send Now !

LEAVE A MESSAGE

Contact us!
We're not around but we still want to hear from you! Leave us a note:

* indicates a required field